Helmholz Analog output module – AO 4 x U, ±10 V, 0–10 V, 1–5 V, 12 Bit
Parameters for the module Diagnostic alarm: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each channel Wire break detection: On | Off...
Trenutno nema na stanju
Parameters for the module
- Diagnostic alarm: On | Off
- Representation values: SIMATIC* S7 | SIMATIC* S5
Parameters for each channel
- Wire break detection: On | Off
- Output range: ±10 V | 0–10 V | 1–5 V
- Substitute value functionality: Outputs de-energized | Retain last value | Apply substitute value
- Substitute value: 16 bit analog value (±27648)
- Output range ±10 V, 0–10 V, 1–5 V
- Resolution 11 bit + sign
- Substitute value functionality
- Diagnostic messages
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- 4 analog outputs, electrically isolated from the backplane bus
- 4 process output words (4 bytes)
| General information | ||
|---|---|---|
| Order number | 600-261-4AD01 | |
| Article name | AO 4 x U, ±10 V, 0–10 V, 1–5 V, 12 bit | |
| Scope of delivery | AO 4 x U, ±10 V, 0–10 V, 1–5 V, 12 bit | |
| Dimensions (DxWxH) | 110 x 14 x 73 mm | |
| Weight | Approx. 70 g | |
| Number of outputs | 4 | |
| Output ranges | ±10 V, 0–10 V, 1–5 V | |
| Electrical isolation | ||
| from the backplane bus | Yes | |
| Between the channels | No | |
| Current draw | ||
| External | Max. 75 mA | |
| Internal | Max. 24 mA | |
| Power dissipation | Max. 2.4 W | |
| Connection for actuators | 2-wire connection | |
| Load resistance | Min. 1 kohm | |
| Capacitive load | Max. 1 µF | |
| Short-circuit protection | ||
| Short-circuit protection | Yes | |
| Short-circuit current | Max. 25 mA | |
| Measurement resolution | 11 bit + sign | |
| Refresh time | 0.2 ms | |
| Settling time | 0.2 ms for resistive loads, 2.2 ms for capacitive loads, 0.5 ms for inductive loads (<=1 mH), 3.3 ms for inductive loads (<=3.3 mH) | |
| Diagnoses | External reference voltage missing (L+), short circuit to GND, parameter assignment error | |
| Error limits | ||
| Operational error limit in the entire temperature range | ±0.5 % relative to the nominal range | |
| Basic error limit at 25 °C | ±0.3 % relative to the nominal range | |
| Temperature error | ±0.005 %/K relative to the nominal range | |
| Linearity error | ±0.05 %/K relative to the nominal range | |
| Repeating accuracy in steady state at 25 °C | ±0.05 %/K relative to the nominal range | |
| Parameter configuration length | 13 bytes | |
| General error indicator | Red LED | |
| Hot-swap capable | Yes | |
| Ambient conditions | ||
| Ambient temperature | 0 °C … +60 °C | |
| Transport and storage temperature | -20 °C … +80 °C | |
| Relative air humidity | 95 % r H without condensation | |
| Protection rating | IP 20 | |
| Certifications | CE, UL | |
| UL | ||
| Surrounding Air Temperature | 0 °C … +60°C | |
| Pollution degree | 2 | |
| CE | ||
| Noise immunity | DIN EN 61000-6-2 “EMC Immunity” | |
| Interference emission | DIN EN 61000-6-4 “EMC Emission” | |
| Vibration and shock resistance | DIN EN 60068-2-8:2008 “Vibration” DIN, EN 60068-27:2010 “Shock“ | |
| RoHS | Yes | |
| REACH | Yes | |