Helmholz Function module – Energy Meter, 5 A

The energy meter function module can be used to measure all important current and voltage measurement values on 230 V AC networks. Input voltages (3 phases + N)...

Brand: Helmholz
Šifra: 600-255-7BA21
Dostupnost: Proveriti dostupnost
Cena bez pdv-a: 23.148,55
Cena sa pdv-om: 27.778,26
   

The energy meter function module can be used to measure all important current and voltage measurement values on 230 V AC networks. Input voltages (3 phases + N) can be connected directly to the module.
In addition to general status information, the module's configuration can be used to show up to 7 readings in the input image table.
In the event of a system failure, the controllable meter's values will be stored in non-volatile memory.

Parameters for the module

  • Overvoltage / undervoltage threshold
  • Overcurrent threshold
  • Zero transition timeout
  • Enable energy meter
  • 50/60 Hz line frequency
  • 3-wire or 4-wire voltage measurement
  • Process image table input values

Parameters for phases A, B, and C

  • Primary current
  • Secondary current
  • Phase angle error correction (for current transformer phase angle error)
  • Zero crossing, overvoltage / undervoltage , overcurrent diagnoses

Configurable process input image table

  • 7 readings at the same time
  • RMS voltage A,B,C
  • RMS current A,B,C
  • A, B, C, and total real power/energy
  • A, B, C, and total apparent power/energy
  • A, B, C, and total reactive power/energy
  • Frequency
  • A, B, C, and total power factor
  • Phase angle between the voltages or between the currents

Diagnostic messages

  • Phase shift
  • Overvoltage / undervoltage
  • Overcurrent
  • No zero crossing (no phase)
  • Configuration errors

Input currents are coupled through current transformers. The Energy Meter module is designed for a maximum secondary current of 5 A.
Other rated secondary currents, as well as the use of Rogowski coils, are available upon request.

  • Measures current, voltage, power, and energy
  • 1 three-phase or 3 single-phase
  • 3-wire and 4-wire voltage measurements
  • Measures real, reactive, and apparent power and energy
  • Energy meter with gate function; values are storedin the module in a non-volatile manner
  • Configurable process input image table
  • Diagnostic messages
  • Current measurement via 5 A current transformer (secondary current)
General information
  Order number 600-255-7BA21
  Article name Energy Meter, 5 A
  Scope of delivery Energy Meter, 5 A
  Dimensions (DxWxH) 110 x 25 x 73 mm
  Weight Approx. 120 g
Number of inputs Voltage L1, L2, L3, N, Current I1, I2, I3
Voltage Max. 400 V AC
Current Max. 5 A, secondary
from the backplane bus Yes
Diagnoses Undervoltage/overvoltage, Overcurrent, No zero crossing, Phase shift
Parameter configuration length 25/49 bytes
General error indicator Red LED
Internal Max. 150 mA
Power dissipation Max. 2.0 W
Hot-swap capable Yes
Ambient conditions
  Ambient temperature 0 °C … +60 °C
  Transport and storage temperature -20 °C … +80 °C
  Relative air humidity 95 % r H without condensation
  Protection rating IP 20
  Certifications CE, UL pending
CE
  Noise immunity DIN EN 61000-6-2 “EMC Immunity”
  Interference emission DIN EN 61000-6-4 “EMC Emission”
  Vibration and shock resistance DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“
  RoHS Yes
  REACH Yes

Slicni proizvodi:


Helmholz Function module – 4 x Counter Economy 24 V, 1 KHz, 32 bit

Counters are used to detect pulses that are faster than a controller’s cycles, i.e., signals that the controller will be unable to detect properly and that
-
Need to order

(Trenutno nema na stanju)

 
 
11.509,61

Helmholz Function module – 1 x SSI Encoder interface

In terms of hardware, the module's SSI is implemented as a point-to-point connection as defined in the RS-422 standard. Moreover, in order to avoid ground loops,
-
Need to order

(Trenutno nema na stanju)

 
 
20.562,12

Helmholz Function module – Energy Meter, 1 A

The energy meter function module can be used to measure all important current and voltage measurement values on 230 V AC networks. Input voltages (3 phases + N)
-
Need to order

(Trenutno nema na stanju)

 
 
23.148,55

Helmholz Function module – 1 x Counter 24 V, 500 KHz, 32 bit

Counters are used to detect pulses that are faster than a controller’s cycles, i.e., signals that the controller will be unable to detect properly and that
-
Need to order

(Trenutno nema na stanju)

 
 
23.148,55

Helmholz Function module – 1 x Counter , 5 V (RS422), 4 MHz, 32 bit

Counters are used to detect pulses that are faster than a controller’s cycles, i.e., signals that the controller will be unable to detect properly and that
-
Need to order

(Trenutno nema na stanju)

 
 
23.148,55

Helmholz Function module – strain gauge weighing module

The weighing module serves the purpose of measuring and processing signals from weight, torque, or force sensors. The weighing module enables the direct connection
-
Need to order

(Trenutno nema na stanju)

 
 
24.441,76

1