Helmholz Analog input module – AI 4 x U, ±10 V, 0–10 V, 1–5 V, Iso., 16 Bit
Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each...
Cena bez pdv-a: 24.441,76 |
Cena sa pdv-om: 29.330,12 |
Parameters for the module
- Diagnostic alarm: On | Off
- Overflow/underflow diagnosis: On | Off
- Representation values: SIMATIC* S7 | SIMATIC* S5
Parameters for each channel
- Wire break detection (only for 1 ... 5 V): On | Off
- Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
- Measuring ranges: Deactivated | 0 ... 10 V | 1 ... 5 V | ±10 V | ±5 V | ±2.5 V
- Limit value alarms enabled: On | Off
- Upper/lower limit: 16 bit analog value (±27648)
Channel LED signals
Flashing red light |
Parameter assignment error on channel |
|
Solid red light |
Reading overflow/underflow or wire break |
|
Flashing green light |
Reading within overrange |
|
Solid green light |
Channel configured, normal reading |
|
Off |
Channel disabled or module not yet configured |
- Channels electrically isolated from each other and from the backplane bus
- Measuring ranges 0 ... 10 V, 1 ... 5 V, ±10 V, ±5 V, ±2.5 V, individually configurable for each channel
- Measurement resolution: up to 15 bits + sign
- Diagnostic messages
- Wire break detection (for 1 ... 5V)
- Limit value alarms for each channel
- A bi-color LED (blue/red) indicates the module operating status and any malfunctions
- Red/green bi-color LEDs (one for each channel) indicate the channel status
- 4 analog inputs for measuring voltage
- 4 process input words
General information | ||
---|---|---|
Order number | 600-252-7BD01 | |
Article name | AI 4x U ,±10 V, 0–10 V, 1–5 V, Iso., 16 bit | |
Scope of delivery | AI 4x U ,±10 V, 0–10 V, 1–5 V, Iso., 16 bit | |
Dimensions (DxWxH) | 110 x 14 x 73 mm | |
Weight | Approx. 80 g | |
Number of inputs | 4 | |
Electrical isolation | ||
from the backplane bus | Yes | |
Between the channels | Yes | |
Internal | Max. 140 mA | |
Power dissipation | Max. 1 W | |
Measuring ranges / load resistance | 0 ... 10 V / 2 Mohms, 1 ... 5 V / 2 Mohms, ±10 V / 2 Mohms, ±5 V / 2 Mohms, ±2.5 V / 2 Mohms | |
Measuring method | Integration | |
Measurement resolution | 15 bits + sign | |
Interference frequency suppression | None | 10 Hz | 50 Hz | 60 Hz | 400 Hz | |
Refresh rate / conversion rate |
Depends on the interference frequency suppression setting being used: None: 2,5 ms 400 Hz: 8 ms 60 Hz: 51 ms 50 Hz: 60 ms 10 Hz: 160 ms |
|
Diagnoses | Upper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break (for 1 ... 5 V only), parameter assignment error | |
Process alarms | Upper and lower limit per channel | |
Error limits | ||
Operational error limit in the entire temperature range | ±0.2 % relative to the nominal range | |
Basic error limit at 25 °C | ±0.1 % relative to the nominal range | |
Temperature error | ±0.005 %/K relative to the nominal range | |
Linearity error | ±0.05 %/K relative to the nominal range | |
Repeating accuracy in steady state at 25 °C | ±0.05 %/K relative to the nominal range | |
Parameter configuration length | 24 bytes | |
General error indicator | Red LED | |
Hot-swap capable | Yes | |
Ambient conditions | ||
Ambient temperature | 0 °C … +60 °C | |
Transport and storage temperature | -20 °C … +80 °C | |
Relative air humidity | 95 % r H without condensation | |
Protection rating | IP 20 | |
Certifications | CE, UL | |
UL | ||
Surrounding Air Temperature | 0 °C … +60°C | |
Pollution degree | 2 | |
CE | ||
Noise immunity | DIN EN 61000-6-2 “EMC Immunity” | |
Interference emission | DIN EN 61000-6-4 “EMC Emission” | |
Vibration and shock resistance | DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“ | |
RoHS | Yes | |
REACH | Yes |
Slicni proizvodi:
Helmholz Analog input module – AI 2 x I, 0/4–20mA, ±20mA, 12 Bit
Parameters for the module Diagnostic alarm: On | Off Overflow / underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each
-
(Trenutno nema na stanju)
16.423,83
Helmholz Analog output module – AO 2 x I, 0/4–20mA, 12 Bit
Parameters for the module Diagnostic alarm: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each channel Wire break detection: On | Off
-
(Trenutno nema na stanju)
16.682,47
Helmholz Analog input module – AI 4 x I, 0/4–20mA, ±20mA, 12 Bit
Parameters for the module Diagnostic alarm: On | Off Overflow / underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each
-
(Trenutno nema na stanju)
19.915,51
Helmholz Analog input module – AI 2 x I, 0/4–20mA, ±20mA, Iso., 16 Bit
Parameters for the module Diagnostic alarm: On | Off Overflow / underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each
-
(Trenutno nema na stanju)
19.915,51
Helmholz Analog output module – AO 4 x I, 0/4–20mA, 12 Bit
Parameters for the module Diagnostic alarm: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each channel Wire break detection: On | Off
-
(Trenutno nema na stanju)
20.950,08
Helmholz Analog input module – AI 8 x TC, Iso., 16 Bit
Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 (for ±80 mV only)
-
(Trenutno nema na stanju)
42.546,77