Helmholz Analog input module – AI 2/4 x R, RTD, 16 Bit, 2/3/4-wire

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Temperature unit: Celsius...

Brand: Helmholz
Šifra: 600-253-4AD01
Dostupnost: Proveriti dostupnost
Cena bez pdv-a: 23.924,48
Cena sa pdv-om: 28.709,37

Parameters for the module

  • Diagnostic alarm: On | Off
  • Overflow/underflow diagnosis: On | Off
  • Representation values: SIMATIC* S7 | SIMATIC* S5
  • Temperature unit: Celsius x 10 | Fahrenheit x 10 | Kelvin x 10

 

Parameters for each channel

  • Wire break detection: On | Off
  • Interference frequency suppression: None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
  • Measuring ranges: 150 ohms / 300 ohms / 600 ohms / 3000 ohms / 6000 ohms / PT100 / PT1000 / Ni100 / Ni1000 / LGNi1000
  • Sensor type: Disabled | 2-wire | 3-wire (channel 0 only) | 4-wire (channel 0 only)
  • Limit value alarms enabled: On | Off
  • Upper/lower limit: 16 bit analog value (±27648)
  • Measuring ranges: 150 ohms, 300 ohms, 600 ohms, 3,000 ohms, 6,000 ohms, Pt100, Pt1000, Ni100, Ni1000, LG-Ni1000, individually configurable for each channel
  • Can accommodate 2/3/4-wire sensors
  • Measurement resolution: 15 bits + sign
  • Diagnostic messages
  • Wire break detection
  • Limit value alarms for each channel
  • A bi-color LED (blue/red) indicates the module operating status and any malfunctions 
  • 2/4 inputs for measuring resistance, electrically isolated from the backplane bus
  • 4 process input words
General information
  Order number 600-253-4AD01
  Article name AI 2/4x R, RTD, 16 bit, 2/3/4 wire
  Scope of delivery AI 2/4x R, RTD, 16 bit, 2/3/4 wire
  Dimensions (DxWxH) 110 x 14 x 73 mm
  Weight Approx. 70 g
Number of inputs 2/4
Electrical isolation
  from the backplane bus Yes
  Between the channels No
Internal Max. 140 mA
Power dissipation Max. 1 W
Measuring ranges 150 ohms, 300 ohms, 600 ohms, 3000 ohms, 6000 ohms, PT100, PT1000, Ni100, Ni1000, LGNi1000
Measuring method Integration
Measurement resolution 15 bits + sign
Interference frequency suppression None | 10 Hz | 50 Hz | 60 Hz | 400 Hz
Refresh rate / conversion rate Number of active channels x conversion time +16 ms for wire break detection for each channel when activated.
The conversion time will depend on the interference frequency suppression:
None: 8 ms
400 Hz: 45 ms
60 Hz: 109 ms
50 Hz: 128 ms
10 Hz: 342 ms
Diagnoses Upper measuring range limit exceeded (overflow), lower measuring range limit fallen below (underflow), wire break, parameter assignment error
Process alarms Upper and lower limit per channel
Error limits
  Operational error limit in the entire temperature range ±0.5 % relative to the nominal range
  Basic error limit at 25 °C ±0.3 % relative to the nominal range
  Temperature error ±0.005 %/K relative to the nominal range
  Linearity error ±0.05 %/K relative to the nominal range
  Repeating accuracy in steady state at 25 °C ±0.05 %/K relative to the nominal range
Parameter configuration length 26 bytes
General error indicator Red LED
Hot-swap capable Yes
Ambient conditions
  Ambient temperature 0 °C … +60 °C
  Transport and storage temperature -20 °C … +80 °C
  Relative air humidity 95 % r H without condensation
  Protection rating IP 20
  Certifications CE, UL
UL
  Surrounding Air Temperature 0 °C … +60°C
  Pollution degree 2
CE
  Noise immunity DIN EN 61000-6-2 “EMC Immunity”
  Interference emission DIN EN 61000-6-4 “EMC Emission”
  Vibration and shock resistance DIN EN 60068-2-8:2008 “Vibration”, DIN EN 60068-27:2010 “Shock“
  RoHS Yes
  REACH Yes

Slicni proizvodi:


Helmholz Analog input module – AI 2 x I, 0/4–20mA, ±20mA, 12 Bit

Parameters for the module Diagnostic alarm: On | Off Overflow / underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each
-
Need to order

(Trenutno nema na stanju)

 
 
16.423,83

Helmholz Analog input module – AI 1/2 x R, RTD, 16 Bit, 2/3/4-wire

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Temperature unit: Celsius
-
Need to order

(Trenutno nema na stanju)

 
 
20.562,12

Helmholz Analog input module – AI 2 x TC, Iso., 16 Bit

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 (for ±80 mV only)
-
Need to order

(Trenutno nema na stanju)

 
 
21.855,33

Helmholz Analog input module – AI 4 x U, ±24 V, 0–24 V, 12 Bit

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 Parameters for each
-
Need to order

(Trenutno nema na stanju)

 
 
23.924,48

Helmholz Analog input module – AI 4 x TC, Iso., 16 Bit

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 (for ±80 mV only)
-
Need to order

(Trenutno nema na stanju)

 
 
25.734,98

Helmholz Analog input module – AI 8 x TC, Iso., 16 Bit

Parameters for the module Diagnostic alarm: On | Off Overflow/underflow diagnosis: On | Off Representation values: SIMATIC* S7 | SIMATIC* S5 (for ±80 mV only)
-
Need to order

(Trenutno nema na stanju)

 
 
42.546,77

1
2
3
Uporedi proizvode Ukloni sve proizvode