Circuit breaker basic frame, ComPacT NSX400L, 150kA/415VAC, 3 poles, 400A frame rating, without trip unit
Main
range |
ComPacT new generation |
product name |
ComPacT NSX new generation |
device short name |
NSX400L |
product or component type |
Basic frame |
device application |
Distribution |
poles description |
3P |
[In] rated current |
400 A at 40 °C |
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
network type |
AC |
network frequency |
50/60 Hz |
suitability for isolation |
Yes conforming to EN/IEC 60947-2 |
utilisation category |
Category A |
[Icu] rated ultimate short-circuit breaking capacity |
130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level |
L 150 kA 415 V AC |
control type |
Toggle |
mounting mode |
Fixed |
Complementary
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
12 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
12 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability |
15000 cycles conforming to IEC 60947-2 |
electrical durability |
12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 |
mounting support |
Backplate |
upside connection |
Front |
downside connection |
Front |
connection pitch |
45 mm |
protection type |
Without protection |
Width (W) |
140 mm |
Height (H) |
255 mm |
Depth (D) |
110 mm |
Environment
standards |
EN/IEC 60947-2
UL 508 |
product certifications |
CSA
UL |
pollution degree |
3 conforming to IEC 60664-1 |
IP degree of protection |
IP40 conforming to IEC 60529 |
IK degree of protection |
IK07 conforming to IEC 62262 |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-50…85 °C |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
4.548 kg |
Package 1 Height |
15.0 cm |
Package 1 width |
15.5 cm |
Package 1 Length |
29.0 cm |
Unit Type of Package 2 |
P12 |
Number of Units in Package 2 |
36 |
Package 2 Weight |
178.0 kg |
Package 2 Height |
43.0 cm |
Package 2 width |
80.0 cm |
Package 2 Length |
120.0 cm |