Circuit breaker, ComPacT NSXm 100E, 16kA/415VAC, 3 poles, TMD trip unit 16A, EverLink lugs
Main
range |
ComPacT new generation |
product name |
ComPacT NSXm new generation |
range of product |
ComPacT NSXm new generation |
device short name |
NSXm 100E |
product or component type |
Circuit breaker |
device application |
Distribution |
poles description |
3P |
protected poles description |
3D |
[In] rated current |
16 A at 40 °C |
[Ue] rated operational voltage |
690 V AC 50/60 Hz |
network type |
AC |
network frequency |
50/60 Hz |
suitability for isolation |
Yes conforming to IEC 60947-2 |
utilisation category |
Category A |
[Icu] rated ultimate short-circuit breaking capacity |
25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level |
E 16 kA 415 V AC |
trip unit name |
TM-D |
trip unit technology |
Thermal-magnetic |
trip unit protection functions |
LI |
control type |
Toggle |
Circuit breaker mounting mode |
Fixed |
Complementary
[Ui] rated insulation voltage |
800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage |
8 kV |
[Ics] rated service short-circuit breaking capacity |
25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability |
20000 cycles |
electrical durability |
20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In |
power dissipation per pole |
2.4 W |
mounting support |
Backplate |
mounting position |
Horizontal and vertical
Flat on the back |
upside connection |
Front |
downside connection |
Front |
Connection terminals |
1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper
1 Everlink lug wire size 2.5…70 mm², flexible copper |
connection pitch |
35 mm with spreaders
27 mm without spreaders |
9 mm pitches |
9 module |
trip unit rating |
16 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable |
[Ir] long-time protection pick-up adjustment range |
0.7...1 x In |
Long-time protection delay adjustment type tr |
Fixed |
Instantaneous protection pick-up adjustment type Ii |
Fixed |
[Ii] instantaneous protection pick-up adjustment range |
500 A |
earth-leakage protection |
Without |
Number of slots for electrical auxiliaries |
1 slot(s) for auxiliary switch OF
1 slot(s) for alarm switch SD
1 slot(s) for voltage release MN or MX |
local signalling |
Flag (green) for presence of auxiliary contacts |
Width (W) |
81 mm |
Height (H) |
137 mm |
Depth (D) |
80 mm |
net weight |
1.06 kg |
colour |
Grey (RAL 7016) |
Environment
standards |
EN/IEC 60947 |
pollution degree |
3 conforming to IEC 60664-1 |
IP degree of protection |
IP40 conforming to IEC 60529 |
IK degree of protection |
IK07 conforming to IEC 62262 |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-50…85 °C |
relative humidity |
0…95 % |
operating altitude |
2000 m without derating
5000 m with derating |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
1.21 kg |
Package 1 Height |
12.0 cm |
Package 1 width |
9.0 cm |
Package 1 Length |
21.0 cm |
Unit Type of Package 2 |
S03 |
Number of Units in Package 2 |
9 |
Package 2 Weight |
11.28 kg |
Package 2 Height |
30.0 cm |
Package 2 width |
30.0 cm |
Package 2 Length |
40.0 cm |