Schneider Electric Prekidač ComPacT NSX630HB2, 100 kA na 690 VAC, MicroLogic 5.3 E zaštitna jedinica 630 A, 3P 3d;C63W35E630
Circuit breaker, ComPacT NSX630HB2, 100kA/690VAC, 3 poles, MicroLogic 5.3E trip unit 630A...
VAT-exclusive price: 370.218,00 |
VAT-inclusive price: 444.261,60 |
Circuit breaker, ComPacT NSX630HB2, 100kA/690VAC, 3 poles, MicroLogic 5.3E trip unit 630A
range | ComPacT new generation |
---|---|
product name | ComPacT NSX new generation |
device short name | NSX630HB2 |
product or component type | Circuit breaker |
device application | Distribution |
poles description | 3P |
protected poles description | 3D |
[In] rated current | 630 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity |
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | HB2 100 kA 690 V AC |
trip unit name | Micrologic 5.3 E |
trip unit technology | Electronic |
trip unit protection functions | LSI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity |
100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability | 15000 cycles |
electrical durability |
8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In |
power dissipation per pole | 39.69 W |
mounting support | Backplate |
mounting position |
Horizontal and vertical Flat on the back |
upside connection | Front |
downside connection | Front |
connection pitch | 45 mm |
protection type |
L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection |
trip unit rating | 630 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range | 250...630 A |
Long-time protection delay adjustment type tr | Adjustable |
[tr] long-time protection delay adjustment range |
15…400 s at 1.5 x Ir 0.5…16 s at 6 x Ir 0.35…11 s at 7.2 x Ir |
thermal memory | 20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
Short-time protection delay adjustment type tsd | Adjustable 5 settings |
[tsd] Short-time protection delay adjustment range |
0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Instantaneous protection pick-up adjustment type Ii | Adjustable |
[Ii] instantaneous protection pick-up adjustment range | 1.5...11 x In |
earth-leakage protection | Without |
zone selective interlocking ZSI | With |
Number of slots for electrical auxiliaries | 6 slot(s) |
local signalling |
Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
display type | LCD display |
type of measurement | Energy meter |
communication of data |
Energy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Power quality Maintenance indicators Demand current and power Maximeters/minimeters |
Width (W) | 140 mm |
Height (H) | 255 mm |
Depth (D) | 110 mm |
net weight | 6.2 kg |
standards | EN/IEC 60947 |
---|---|
product certifications |
CCC EAC Marine |
overvoltage category | Class II |
electrical shock protection class | Class II |
pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -40…85 °C |
relative humidity | 0…95 % |
operating altitude |
0...2000 m without derating 2000 m...5000 m with derating |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 5.52 kg |
Package 1 Height | 15.2 cm |
Package 1 width | 15.2 cm |
Package 1 Length | 29.2 |
range | ComPacT new generation |
---|---|
product name | ComPacT NSX new generation |
device short name | NSX630HB2 |
product or component type | Circuit breaker |
device application | Distribution |
poles description | 3P |
protected poles description | 3D |
[In] rated current | 630 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity |
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | HB2 100 kA 690 V AC |
trip unit name | Micrologic 5.3 E |
trip unit technology | Electronic |
trip unit protection functions | LSI |