Circuit breaker, ComPacT NSX630HB1, 75kA/690VAC, 3 poles, MicroLogic 2.3M trip unit 500A
Main
range |
ComPacT new generation |
product name |
ComPacT NSX new generation |
device short name |
NSX630HB1 |
product or component type |
Circuit breaker |
device application |
Motor protection |
poles description |
3P |
protected poles description |
3D |
[In] rated current |
500 A at 65 °C |
[Ue] rated operational voltage |
690 V AC 50/60 Hz |
network type |
AC |
network frequency |
50/60 Hz |
suitability for isolation |
Yes conforming to EN/IEC 60947-2 |
utilisation category |
Category A |
[Icu] rated ultimate short-circuit breaking capacity |
85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level |
HB1 75 kA 690 V AC |
trip unit name |
Micrologic 2.3 M |
trip unit technology |
Electronic |
trip unit protection functions |
LSoI |
control type |
Toggle |
Circuit breaker mounting mode |
Fixed |
Complementary
[Ui] rated insulation voltage |
800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage |
8 kV |
[Ics] rated service short-circuit breaking capacity |
85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability |
15000 cycles |
electrical durability |
8000 cycles at 440 V In/2
4000 cycles at 440 V In
6000 cycles at 690 V In/2
2000 cycles at 690 V In |
power dissipation per pole |
25 W |
mounting support |
Backplate |
mounting position |
Horizontal and vertical
Flat on the back |
upside connection |
Front |
downside connection |
Front |
connection pitch |
45 mm |
protection type |
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection |
trip unit rating |
500 A at 65 °C |
motor tripping class |
20
10
5 |
complementary motor protection |
Phase unbalance |
Long-time pick-up adjustment type Ir (thermal protection) |
Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range |
250...500 A |
Long-time protection delay adjustment type tr |
Fixed |
[tr] long-time protection delay adjustment range |
120 s at 1.5 x Ir for trip class 5
6.5 s at 6 x Ir for trip class 5
5 s at 7.2 x Ir for trip class 5
240 s at 1.5 x Ir for trip class 10
13.5 s at 6 x Ir for trip class 10
10 s at 7.2 x Ir for trip class 10
480 s at 1.5 x Ir for trip class 20
26 s at 6 x Ir for trip class 20
20 s at 7.2 x Ir for trip class 20 |
thermal memory |
20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd |
Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range |
5...13 x Ir |
Short-time protection delay adjustment type tsd |
Fixed |
Instantaneous protection pick-up adjustment type Ii |
Fixed |
[Ii] instantaneous protection pick-up adjustment range |
6500 A |
earth-leakage protection |
Without |
zone selective interlocking ZSI |
Without |
Number of slots for electrical auxiliaries |
6 slot(s) |
local signalling |
Flashing LED (green) for ready to operate
LED 95 % Ith (red) for temperature over set point |
Width (W) |
140 mm |
Height (H) |
255 mm |
Depth (D) |
110 mm |
net weight |
6.2 kg |
Environment
standards |
EN/IEC 60947 |
product certifications |
CCC
EAC
Marine |
overvoltage category |
Class II |
electrical shock protection class |
Class II |
pollution degree |
3 conforming to IEC 60664-1 |
IP degree of protection |
IP40 conforming to IEC 60529 |
IK degree of protection |
IK07 conforming to IEC 62262 |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-50…85 °C |
relative humidity |
0…95 % |
operating altitude |
0...2000 m without derating
2000 m...5000 m with derating |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
5.773 kg |
Package 1 Height |
15.2 cm |
Package 1 width |
15.2 cm |
Package 1 Length |
29.2 cm |