Circuit breaker, ComPacT NSX100F AC/DC, 18kA/415VAC, 2 poles, TMD trip unit 16A
Main
range |
ComPacT new generation |
product name |
ComPacT NSX new generation |
device short name |
NSX100F |
product or component type |
Circuit breaker |
device application |
Distribution |
poles description |
2P |
protected poles description |
2D |
[In] rated current |
16 A at 40 °C |
[Ue] rated operational voltage |
690 V AC 50/60 Hz
500 V DC |
network type |
AC
DC |
network frequency |
50/60 Hz |
suitability for isolation |
Yes conforming to EN/IEC 60947-2 |
utilisation category |
Category A |
[Icu] rated ultimate short-circuit breaking capacity |
36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2
10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2
5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2
36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2 |
Performance level |
F 18 kA 415 V AC |
trip unit name |
TM-D |
trip unit technology |
Thermal-magnetic |
trip unit protection functions |
LI |
control type |
Toggle |
Circuit breaker mounting mode |
Fixed |
Complementary
[Ui] rated insulation voltage |
750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2 |
mechanical durability |
20000 cycles |
electrical durability |
20000 cycles at 277 V In/2
10000 cycles at 277 V In |
power dissipation per pole |
2.92 W |
mounting support |
Backplate |
mounting position |
Horizontal and vertical
Flat on the back |
upside connection |
Front |
downside connection |
Front |
connection pitch |
35 mm |
protection type |
L : for overload protection (thermal)
I : for short-circuit protection (magnetic) |
trip unit rating |
16 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) |
Fixed |
[Ir] long-time protection pick-up adjustment range |
1 x In |
Long-time protection delay adjustment type tr |
Fixed |
Instantaneous protection pick-up adjustment type Ii |
Fixed |
[Ii] instantaneous protection pick-up adjustment range |
190 A |
earth-leakage protection |
Without |
Width (W) |
70 mm |
Height (H) |
161 mm |
Depth (D) |
86 mm |
net weight |
1.2 kg |
Environment
standards |
EN/IEC 60947 |
product certifications |
CCC
EAC
Marine |
overvoltage category |
Class II |
electrical shock protection class |
Class II |
pollution degree |
3 conforming to IEC 60664-1 |
IP degree of protection |
IP40 conforming to IEC 60529 |
IK degree of protection |
IK07 conforming to IEC 62262 |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-50…85 °C |
relative humidity |
0…95 % |
operating altitude |
0...2000 m without derating
2000 m...5000 m with derating |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
1.282 kg |
Package 1 Height |
8.0 cm |
Package 1 width |
13.0 cm |
Package 1 Length |
18.0 cm |
Unit Type of Package 2 |
S03 |
Number of Units in Package 2 |
12 |
Package 2 Weight |
15.871 kg |
Package 2 Height |
30.0 cm |
Package 2 width |
30.0 cm |
Package 2 Length |
40.0 cm |