Schneider Electric Pogon promenljive brzine, Altivar Process ATV600, ATV650, 250 kV, 400 ... 480 V, podni;ATV650C25N4F

Schneider Electric Pogon promenljive brzine, Altivar Process ATV600, ATV650, 250 kV, 400 ... 480 V, podni;ATV650C25N4F

Variable speed drive, Altivar Process ATV600, ATV650, 250 kW, 400...480 V, floor standing...

Brand: Schneider Electric
Product Code: ATV650C25N4F
Availability: Check availability
VAT-exclusive price: 3.632.940,00
VAT-inclusive price: 4.359.528,00

Variable speed drive, Altivar Process ATV600, ATV650, 250 kW, 400...480 V, floor standing

 
 

Main
range of product Altivar Process ATV600
product or component type Variable speed drive
product specific application Process and utilities
device short name ATV650
variant With disconnect switch
product destination Synchronous motors
Asynchronous motors
EMC filter Integrated with 150 m conforming to EN/IEC 61800-3 category C3
IP degree of protection IP54 conforming to IEC 60529
IP54 conforming to IEC 61800-5-1
[Us] rated supply voltage 380...440 V
type of cooling Forced convection
supply frequency 50...60 Hz - 5...5 %
[Us] rated supply voltage 380...440 V - 15...10 %
motor power kW 250 kW (normal duty)
200 kW (heavy duty)
line current 391 A at 400 V (heavy duty)
319 A at 380 V (normal duty)
453 A at 380 V (heavy duty)
369 A at 400 V (normal duty)
prospective line Isc 50 kA
apparent power 298 kVA at 440 V (normal duty)
243 kVA at 440 V (heavy duty)
continuous output current 477 A at 2.5 kHz for normal duty
370 A at 2.5 kHz for heavy duty
maximum transient current 525 A during 60 s (normal duty)
555 A during 60 s (heavy duty)
asynchronous motor control profile Optimized torque mode
Constant torque standard
Variable torque standard
synchronous motor control profile Synchronous reluctance motor
Permanent magnet motor
speed drive output frequency 0.1…500 Hz
nominal switching frequency 2.5 kHz
switching frequency 2...8 kHz adjustable
2.5...8 kHz with derating factor
safety function STO (safe torque off) SIL 3
discrete input logic 16 preset speeds
communication port protocol Modbus TCP
Ethernet
Ethernet
option card Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Slot A: communication module, Profibus DP V1
Complementary
mounting mode Floor-standing
network number of phases 3 phases
discrete output number 0
discrete output type Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
output voltage <= power supply voltage
permissible temporary current boost 1.5 x In during 60 s (heavy duty)
1.1 x In during 60 s (normal duty)
motor slip compensation Not available in permanent magnet motor law
Automatic whatever the load
Adjustable
Can be suppressed
acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s
physical interface Ethernet
2-wire RS 485
braking to standstill By DC injection
protection type Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Thermal protection: motor
transmission rate 10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
frequency resolution Analog input: 0.012/50 Hz
Display unit: 0.1 Hz
transmission frame RTU
electrical connection Line side: M12 bar - 2 cables 3 x 120 mm² minimum per phase (normal duty)
Line side: M12 bar - 3 cables 3 x 70 mm² minimum per phase (normal duty)
Line side: M12 bar - 3 cables 3 x 185 mm² maximum per phase (normal duty)
Line side: M12 bar - 4 cables 3 x 120 mm² maximum per phase (normal duty)
Motor: M12 bar - 2 cables 3 x 120 mm² minimum per phase (normal duty)
Motor: M12 bar - 3 cables 3 x 70 mm² minimum per phase (normal duty)
Motor: M12 bar - 3 cables 3 x 185 mm² maximum per phase (normal duty)
Motor: M12 bar - 4 cables 3 x 120 mm² maximum per phase (normal duty)
Line side: M12 bar - 2 cables 3 x 95 mm² minimum per phase (heavy duty)
Line side: M12 bar - 3 cables 3 x 185 mm² maximum per phase (heavy duty)
Line side: M12 bar - 4 cables 3 x 120 mm² maximum per phase (heavy duty)
Motor: M12 bar - 1 cables 3 x 185 mm² minimum per phase (heavy duty)
Motor: M12 bar - 2 cables 3 x 95 mm² minimum per phase (heavy duty)
Motor: M12 bar - 3 cables 3 x 185 mm² maximum per phase (heavy duty)
Motor: M12 bar - 4 cables 3 x 120 mm² maximum per phase (heavy duty)
Control: removable screw terminals 0.5...1.5 mm²
connector type RJ45 (on the remote graphic terminal) for Modbus serial
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
data format 8 bits, configurable odd, even or no parity
type of polarization No impedance
exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
number of addresses 1…247 for Modbus serial
method of access Slave Modbus TCP
supply Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
local signalling 3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
3 LEDs for local diagnostic
width 600 mm
height 2350 mm
depth 669 mm
net weight 420 kg
analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
discrete input number 8
discrete input type DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
discrete input logic Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
analogue output number 2
analogue output type Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
sampling duration 5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
2 ms +/- 0.5 ms (DI1...DI4) - discrete input
accuracy +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
linearity error AO1, AO2: +/- 0.2 % for analog output
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
relay output number 3
relay output type Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
isolation Between power and control terminals
maximum output frequency 500 kHz
maximum input current 453.0 A
Variable speed drive application selection Food and beverage processing Other application
Mining mineral and metal Fan
Mining mineral and metal Pump
Oil and gas Fan
Water and waste water Other application
Building - HVAC Screw compressor
Food and beverage processing Pump
Food and beverage processing Fan
Food and beverage processing Atomization
Oil and gas Electro submersible pump (ESP)
Oil and gas Water injection pump
Oil and gas Jet fuel pump
Oil and gas Compressor for refinery
Water and waste water Centrifuge pump
Water and waste water Positive displacement pump
Water and waste water Electro submersible pump (ESP)
Water and waste water Screw pump
Water and waste water Lobe compressor
Water and waste water Screw compressor
Water and waste water Compressor centrifugal
Water and waste water Fan
Water and waste water Conveyor
Water and waste water Mixer
Building - HVAC Compressor centrifugal
Motor power range AC-3 110…220 kW at 480…500 V 3 phases
250…500 kW at 380…440 V 3 phases
quantity per set 1
enclosure mounting Floor-standing
Environment
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level

Similar products:


Schneider Electric increased protection degree IP54, Altivar Process ATV600, Altivar Process ATV900, for Drive Systems 355 to 500kW; VW3AP0303

increased protection degree IP54, Altivar Process ATV600, Altivar Process ATV900, for Drive Systems 355 to 500kW; VW3AP0303
-
Need to order

(Out of stock)

 
 
127.094,80

Schneider Electric Pogon promenljive brzine, Altivar Process ATV600, ATV650, 132 kV, 400 ... 480 V, podno stajanje;ATV650C13N4F

Variable speed drive, Altivar Process ATV600, ATV650, 132 kW, 400...480 V, floor standing
-
Need to order

(Out of stock)

 
 
2.179.766,00

Schneider Electric Pogon sa promenljivom brzinom, Altivar Process ATV600, ATV650, 160 kV, 400 ... 480 V, podno stajanje;ATV650C16N4F

Variable speed drive, Altivar Process ATV600, ATV650, 160 kW, 400...480 V, floor standing
-
Need to order

(Out of stock)

 
 
2.421.960,00

Schneider Electric Pogon sa promenljivom brzinom, Altivar Process ATV600, ATV650, 200 kW, 380- 440 V, IP54, prekidač za isključivanje;ATV650C20N4F

Variable speed drive, Altivar Process ATV600, ATV650, 200 kW, 380...440 V, IP54, disconnect switch
-
Need to order

(Out of stock)

 
 
3.027.448,00

Schneider Electric Pogon sa promenljivom brzinom, Altivar Process ATV600, ATV630, 250 kV, 380 ... 440 V, IP21;ATV630C25N4F

Variable speed drive, Altivar Process ATV600, ATV630, 250 kW, 380...440 V, IP21
-
Need to order

(Out of stock)

 
 
3.407.363,00

Schneider Electric Pogon sa promenljivom brzinom, Altivar Process ATV600, ATV650, 315 kV, 400 ... 480 V, podno stajanje;ATV650C31N4F

Variable speed drive, Altivar Process ATV600, ATV650, 315 kW, 400...480 V, floor standing
-
Need to order

(Out of stock)

Price on request

ELECTRO PNEUMATIC SOLUTIONS DOO

  • Jugoslovenska 2/13A, Čukarica, Beograd
  • Opening Times: Monday - Friday 8am-5pm
  • Telephone:
  • 011 257 1922
  • +381 64 659 66 55
  • +381 62 800 70 44
  • email: office@ep-solutions.rs

linkedin youtube instagram twitter facebook
1
2
3
Compare products Remove all products