miniature circuit breaker - C60H - 1 pole - 10 A - C curve
Main
range |
Acti 9 |
product name |
Acti9 C60H-DC |
product or component type |
Miniature circuit-breaker |
device short name |
C60H-DC |
device application |
Distribution |
poles description |
1P |
number of protected poles |
1 |
[In] rated current |
10 A at 25 °C |
network type |
DC |
trip unit technology |
Thermal-magnetic |
curve code |
C |
breaking capacity |
10 kA Icu at 220 V DC conforming to EN 60947-2
10 kA Icu at 220 V DC conforming to IEC 60947-2
6 kA Icu at 250 V DC conforming to EN 60947-2
6 kA Icu at 250 V DC conforming to IEC 60947-2
20 kA Icu at 110 V DC conforming to EN 60947-2
20 kA Icu at 110 V DC conforming to IEC 60947-2 |
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
suitability for isolation |
Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2 |
Complementary
network frequency |
50/60 Hz |
[Ue] rated operational voltage |
250 V DC |
[Ics] rated service breaking capacity |
15 kA 75 % conforming to EN 60947-2 - 110 V DC
15 kA 75 % conforming to IEC 60947-2 - 110 V DC
4.5 kA 75 % conforming to EN 60947-2 - 250 V DC
4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC
7.5 kA 75 % conforming to EN 60947-2 - 220 V DC
7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC |
[Ui] rated insulation voltage |
500 V DC conforming to IEC 60947-2
500 V DC conforming to EN 60947-2 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
contact position indicator |
Yes |
control type |
Toggle |
local signalling |
ON/OFF indication |
mounting mode |
Fixed |
mounting support |
35 mm symmetrical DIN rail |
comb busbar and distribution block compatibility |
Top or bottom: standard |
9 mm pitches |
2 |
net weight |
0.128 kg |
colour |
White |
mechanical durability |
20000 cycles |
electrical durability |
3000 cycles 250 V DC
6000 cycles 250 V DC |
provision for padlocking |
Padlockable |
locking options description |
In position O |
tightening torque |
Power circuit: 2.5 N.m top or bottom |
earth-leakage protection |
Without |
Environment
standards |
EN 60947-2
IEC 60947-2 |
pollution degree |
3 conforming to EN 60947-2
3 conforming to IEC 60947-2 |
overvoltage category |
IV |
tropicalisation |
2 conforming to IEC 60068-2 |
operating altitude |
2000 m |
ambient air temperature for operation |
-25…70 °C |
ambient air temperature for storage |
-40…85 °C |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Weight |
112.0 g |
Package 1 Height |
7.0 cm |
Package 1 width |
1.8 cm |
Package 1 Length |
7.5 cm |
Unit Type of Package 2 |
P12 |
Number of Units in Package 2 |
1152 |
Package 2 Weight |
148.28 kg |
Package 2 Height |
80.0 cm |
Package 2 width |
80.0 cm |
Package 2 Length |
120.0 cm |
Unit Type of Package 3 |
BB1 |
Number of Units in Package 3 |
12 |
Package 3 Weight |
1.379 kg |
Package 3 Height |
2.65 cm |
Package 3 width |
30.0 cm |
Package 3 Length |
20.0 cm |
Contractual warranty
Warranty |
18 months |