45 mm wide only , TeSys Ultra all-in-one motor starters protect and control motors forward and reverse.
Choice of control voltages (electronic coils) :
- 24 V AC / DC, low consumption
- 48…72 V DC / 48 V AC
-
110..220 V DC / 110...240 V AC
Short-circuit protection:
- 50 kA Icu, up to 32 A (15 kW motors) under 400 V
- 25 kA Icu at 38A (18,5 kW motors)
-
Total coordination (IEC 60 947-6-2) as standard
Overload protection:
LUCM multi-function control unit (up to 32A rating) features a user interface for advanced diagnosis and control.
Displays :
Settings :
- 6 setting ranges, altogether covering all ratings from 0.15 to 32 A,
- Choice of tripping classes (tripping times): 10, 20, or selectable 5 thru 30
- Test button
- Instantaneous currents
- Number of trips and types of the last 5
- Number of starts, of operating hours
- Selection of protection pre-alarms
- Short-circuit tripping current
- Phase unbalance tripping threshold
- Thermal protection class (tipping times)
-
Jammed rotor and under-current protections
Various options through additional plug-and-play modules:
- Auxiliary contacts
- Motor load / overload monitoring
-
Digital communication (Modbus, Ethernet, CANopen, etc.)
Reverse starter in 45 mm only frame